  "id": 454,
  "url": "https://nnemf.org/research/454-passive-techniques-for-magnetic-field-mitigation-in-underground",
  "title": "Passive Techniques for Magnetic Field Mitigation in Underground Power",
  "authors": [],
  "journal": "",
  "year": "2023",
  "doi": "10.1109/ecti-con58255.2023.10153381",
  "pmid": null,
  "abstract": "Passive Techniques for Magnetic Field Mitigation in Underground Power Systems",
  "effect": "benefit",
  "evidence": "low",
  "extraction": {
    "studyType": "engineering",
    "studyTypeLabel": "engineering",
    "effectDirection": "benefit",
    "evidenceLabel": "Low",
    "population": "—",
    "sampleSize": "—",
    "exposure": "ELF <1 MHz",
    "confidencePct": "74",
    "peerReviewed": "unknown",
    "mainFindings": "Finite-element simulations (FEMM) compared magnetic fields with and without passive mitigation (conductive loop, conductive shield, ferromagnetic shield) for a 69/115 kV underground power system. All simulated techniques reduced magnetic field values to below the referenced ICNIRP/European standards, with results reported as below 10 µT; conductive and ferromagnetic shields mitigated more than a conductive loop.",
    "outcomes": [
      "Magnetic field level reduction (µT)",
      "Compliance with ICNIRP and European reference values"
    ],
    "limitations": [
      "Simulation study (FEMM) rather than field measurements",
      "Results stated to be limited by construction conditions (not further specified in abstract)",
      "No quantitative baseline field values reported in the abstract beyond the post-mitigation level (<10 µT)"
    ],
    "keywords": [
      "magnetic field mitigation",
      "underground power system",
      "69 kV",
      "115 kV",
      "ELF magnetic fields",
      "conductive loop",
      "conductive shield",
      "ferromagnetic shield",
      "FEMM",
      "ICNIRP",
      "European standards"
    ],
    "hubs": [
      {
        "slug": "occupational-exposure",
        "weight": "0.7",
        "reason": "Focuses on mitigation of low-frequency magnetic fields from power infrastructure; potentially relevant to occupational/public exposure near underground cables."
      },
      {
        "slug": "who-icnirp",
        "weight": "0.7",
        "reason": "Explicitly references ICNIRP reference values/standards for magnetic field limits."
      }
    ],
    "raw": "{\n  \"study_type\": \"engineering\",\n  \"exposure\": {\n    \"band\": \"ELF\",\n    \"source\": \"underground power system (69/115 kV cables)\",\n    \"frequency_mhz\": null,\n    \"sar_wkg\": null,\n    \"duration\": null\n  },\n  \"population\": null,\n  \"sample_size\": null,\n  \"outcomes\": [\n    \"Magnetic field level reduction (µT)\",\n    \"Compliance with ICNIRP and European reference values\"\n  ],\n  \"main_findings\": \"Finite-element simulations (FEMM) compared magnetic fields with and without passive mitigation (conductive loop, conductive shield, ferromagnetic shield) for a 69/115 kV underground power system. All simulated techniques reduced magnetic field values to below the referenced ICNIRP/European standards, with results reported as below 10 µT; conductive and ferromagnetic shields mitigated more than a conductive loop.\",\n  \"effect_direction\": \"benefit\",\n  \"limitations\": [\n    \"Simulation study (FEMM) rather than field measurements\",\n    \"Results stated to be limited by construction conditions (not further specified in abstract)\",\n    \"No quantitative baseline field values reported in the abstract beyond the post-mitigation level (<10 µT)\"\n  ],\n  \"evidence_strength\": \"low\",\n  \"confidence\": 0.74,\n  \"peer_reviewed_likely\": \"unknown\",\n  \"keywords\": [\n    \"magnetic field mitigation\",\n    \"underground power system\",\n    \"69 kV\",\n    \"115 kV\",\n    \"ELF magnetic fields\",\n    \"conductive loop\",\n    \"conductive shield\",\n    \"ferromagnetic shield\",\n    \"FEMM\",\n    \"ICNIRP\",\n    \"European standards\"\n  ],\n  \"suggested_hubs\": [\n    {\n      \"slug\": \"occupational-exposure\",\n      \"weight\": 0.25,\n      \"reason\": \"Focuses on mitigation of low-frequency magnetic fields from power infrastructure; potentially relevant to occupational/public exposure near underground cables.\"\n    },\n    {\n      \"slug\": \"who-icnirp\",\n      \"weight\": 0.55,\n      \"reason\": \"Explicitly references ICNIRP reference values/standards for magnetic field limits.\"\n    }\n  ]\n}"
  },
  "synthesis": null,
  "synthesisStatus": "pending",
  "originalHref": "https://ieeexplore.ieee.org/document/10153381",
  "sourceUrl": "https://rfsafe.org/mel/paper.php?id=454",
  "updated": "2026-02-10 10:25:40"
}